9.11 Configurable Data Attributes
9.11.1 System/LLN0
Parameter Default Value
Mod.measCyc Value 5
Transmission of measured values: Time interval in seconds between two dead
band evaluations.
Parameter Default Value
Mod.enCyc Value 65535
Cyclic transmission of measured values without dead band check: Time interval
in seconds between transmissions of two energy count values.
Parameter Default Value
Mod.comtrade Value BINARY
Transmission of COMTRADE fault files formatted either as ASCII or binary files.
Parameter Default Value
Mod.distExtr Value true
Cancelling fault transmission or including it in the configuration.
P634 9 IEC 61850 Settings via IED Configurator
9-16 P634/EN M/R-42-A // P634311653