8.1.1 Cyclic Values
8.1.1.1 Measured Operating Data
Parameter Address
Default Min Max Unit Logic Diagram
Measured data input
MEASI: Current IDC
004 134
Not measured 0.00 24.00 mA Fig. 3-26, (p. 3-42)
[spacer]
Display of the input current.
[spacer]
MEASI: Current IDC p.u.
004 135
Not measured 0.00 1.20 IDC,nom Fig. 3-26, (p. 3-42)
[spacer]
Display of the input current referred to I
DC,nom
.
[spacer]
MEASI: Curr. IDC,lin. p.u.
004 136
Not measured 0.00 1.20 IDC,nom Fig. 3-26, (p. 3-42)
[spacer]
Display of the linearized input current referred to I
DC,nom
.
[spacer]
MEASI: Scaled value IDC,lin
004 180
Not measured -32000 32000 Fig. 3-27, (p. 3-43)
[spacer]
Display of the scaled linearized value.
[spacer]
MEASI: Temperature
004 133
Not measured -40.0 215.0 °C Fig. 3-28, (p. 3-44)
[spacer]
Display of the temperature measured at the “PT 100” temperature input on the
analog p/c board.
[spacer]
MEASI: Temperature p.u.
004 221
Not measured -0.40 2.15 100°C Fig. 3-28, (p. 3-44)
[spacer]
Display of the temperature measured at the “PT 100” temperature input on the
analog p/c board referred to 100°C.
[spacer]
MEASI: Temperature Tmax
004 233
Not measured -40.0 215.0 °C Fig. 3-28, (p. 3-44)
[spacer]
Display of the maximum temperature measured at the “PT 100” temperature
input on the analog p/c board.
P634 8 Information and Control Functions