3.23.5 General Starting
If the current exceeds one of the set thresholds of the phase current stages, a
general starting decision is issued. The user can select whether the starting of
the negative-sequence and residual current stages should be taken into account
in the general starting decision. The general starting triggers a timer stage. A
signal is issued when the time delay of this stage has elapsed.
64Z5025A
DTOC1:
tGS elapsed
[ 035 129 ]
DTOC1:
General starting
[ 035 128 ]
Parameter
set 1
set 2
set 3
set 4
DTOC1:
Gen.starting modePSx
076 066
077 066
078 066
079 066
DTOC1:
tGS PSx
076 065
077 065
078 065
079 065
DTOC1:
Gen.starting modePSx
[ * ]
1
0
0: W/o start. IN/Ineg
1: With start. IN/Ineg
DTOC1:
tGS PSx
[ * ]
DTOC1:
Starting Ineg>
[ 036 145 ]
DTOC1:
Starting Ineg>>
[ 036 146 ]
DTOC1:
Starting Ineg>>>
[ 036 147 ]
DTOC1:
Starting N
[ 035 107 ]
DTOC1:
Starting I>
[ 035 108 ]
DTOC1:
Starting I>>
[ 035 109 ]
DTOC1:
Starting I>>>
[ 035 110 ]
Fig. 3-112: General starting
3.23.6 General Trip Signal
All DTOC trip signals are ORed to form a group signal.
62Z9008A
DTOC1:
Trip signal tI>
[ 035 114 ]
DTOC1:
Trip signal
[ 019 215 ]
DTOC1:
Trip signal tI>>
[ 035 115 ]
DTOC1:
Trip signal tI>>>
[ 035 116 ]
DTOC1:
Trip signal tIneg>
[ 036 151 ]
DTOC1:
Trip signal tIneg>>
[ 036 152 ]
DTOC1:
Trip signal tIneg>>>
[ 036 153 ]
DTOC1:
Trip signal tIN>
[ 035 126 ]
DTOC1:
Trip signal tIN>>
[ 035 130 ]
DTOC1:
Trip signal tIN>>>
[ 035 131 ]
Fig. 3-113: Trip signal