EasyManua.ls Logo

Micom P634 - IRIG-B Interface; Direct Current Input; Resistance Thermometer; Direct Current Output

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.5.3 IRIG‑B Interface
●
Minimum / maximum input voltage level (peak-peak): 100 mVpp / 20 Vpp
●
Input impedance: 33 kΩ at 1 kHz
●
Electrical isolation: 2 kV
2.5.4 Direct Current Input
●
Input current: 0 to 26 mA
●
Value range: 0.00 to 1.20 I
DC,nom
(I
DC,nom
= 20 mA)
●
Maximum continuous input current permitted: 50 mA
●
Maximum input voltage permitted: 17 V DC
●
Input load: 100 Ω
●
Open-circuit monitoring: 0 to 10 mA (adjustable)
●
Overload monitoring: > 24.8 mA
●
Zero suppression: 0.000 to 0.200 I
DC,nom
(adjustable).
2.5.5 Resistance Thermometer
Only PT 100 permitted for analog (I/O) module, mapping curve per IEC 75.1.
PT 100, Ni 100 or Ni 120 permitted for temperature p/c board (the RTD module).
●
Value range: ‑40.0°C to +215.0°C (‑40°F to +419°F).
●
3-wire configuration: max. 20 Ω per conductor.
●
Open and short-circuited input permitted.
●
Open-circuit monitoring: Θ > +215°C and Θ < -40°C (Θ > +419°F and
Θ < -40°F).
2.5.6 Direct Current Output
●
Output current: 0 to 20 mA
●
Maximum permissible load: 500 Ω
●
Maximum output voltage: 15 V
P634 2 Technical Data
2-12 P634/EN M/R-42-A // P634‑311‑653