EasyManua.ls Logo

Micom P634 - Interfaces; Local Control Panel; PC Interface; Serial Communication Interface

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.6 Interfaces
2.6.1 Local Control Panel
Input or output
●
With 13 keys and a 4 ×20 character liquid crystal display (LCD).
State and fault signals
●
23 LED indicators (5 permanently assigned, 18 freely configurable).
2.6.2 PC Interface
●
Transmission rate: 300 to 115,200 baud (adjustable)
2.6.3 Serial Communication Interface
The communication module can be provided with up to two communication
channels, depending on the module variant. Channel 1 may either be equipped
to connect wire leads or optical fibers and channel 2 is only available to connect
wire leads.
For communication interface 1, communication protocols based on
IEC 870-5‑103, IEC 60870‑5‑101, MODBUS, DNP 3.0, or Courier can be set.
●
Transmission rate: 300 to 64000 baud (adjustable).
Communication interface 2 can only be operated with the interface protocol
based on IEC 60870-5-103.
●
Transmission rate: 300 or 57600 baud (adjustable).
Wire Leads
●
Per RS 485 or RS 422, 2 kV isolation
●
Distance to be bridged
o
Point-to-point connection: max. 1200 m
o
Multipoint connection: max. 100 m
Plastic Fiber Connection
●
Optical wavelength: typically 660 nm
●
Optical output: min. -7.5 dBm
●
Optical sensitivity: min. -20 dBm
●
Optical input: max. -5 dBm
●
Distance to be bridged: max. 45 m
(Distance to be bridged given for identical optical outputs and inputs at
both ends, a system reserve of 3 dB, and typical fiber attenuation)
Glass Fiber Connection G 50/125
●
Optical wavelength: typically 820 nm
●
Optical output: min. -19.8 dBm
●
Optical sensitivity: min. -24 dBm
●
Optical input: max. -10 dBm
●
Distance to be bridged: max. 400 m
(Distance to be bridged given for identical optical outputs and inputs at
both ends, a system reserve of 3 dB, and typical fiber attenuation)
P634
2 Technical Data
2-14 P634/EN M/R-42-A // P634‑311‑653

Table of Contents

Related product manuals