3.24.3 Phase Current Stage
64Z8975A
Parameter
set 1
set 2
set 3
set 4
IDMT1:
Factor kt,P PSx
081 054
082 054
083 054
084 054
IDMT1:
Min. trip t. P PSx
081 057
082 057
083 057
084 057
IDMT1:
Hold time P PSx
081 055
082 055
083 055
084 055
IDMT1:
Release P PSx
081 056
082 056
083 056
084 056
Parameter
set 1
set 2
set 3
set 4
IDMT1:
Rush restr.enabl PSx
081 060
082 060
083 060
084 060
IDMT1:
Iref,P PSx
081 051
082 051
083 051
084 051
IDMT1:
Iref,P dynamic PSx
081 052
082 052
083 052
084 052
IDMT1:
Characteristic P PSx
081 053
082 053
083 053
084 053
0: Definite Time
Setting
1: IEC Standard Inverse
2: IEC Very Inverse
3: IEC Extr. Inverse
4: IEC Long Time Inv.
5: IEEE Moderately Inv.
6: IEEE Very Inverse
7: IEEE Extremely Inv.
8: ANSI Normally Inv.
10: ANSI Long Time Inv.
11: RI-Type Inverse
12: RXIDG-Type Inverse
9: ANSI Short Time Inv.
IDMT1:
Characteristic P PSx
IDMT1:
Characteristic P PSx
[ * ]
IDMT1:
Factor kt,P PSx
[ * ]
IDMT1:
Min. trip t. P PSx
[ * ]
IDMT1:
Hold time P PSx
[ * ]
IDMT1:
Release P PSx
[ * ]
Setting
IDMT1:
Release P PSx
1: Without delay
2: Delayed as per char.
IP,max/Iref,P
IDMT1:
Rush restr.enabl PSx
[ * ]
IDMT1:
Iref,P PSx
[ * ]
IDMT1:
Iref,P dynamic PSx
[ * ]
IDMT1:
Starting Iref,A>
[ 038 117 ]
IDMT1:
Starting Iref,B>
[ 038 118 ]
IDMT1:
Starting Iref,C>
[ 038 119 ]
IDMT1:
Starting Iref,P>
[ 038 110 ]
IDMT1:
tIref,P> elapsed
[ 038 111 ]
IDMT1:
Hold time P running
[ 038 112 ]
IDMT1:
Memory P clear
[ 038 113 ]
0: No
1
0
1: Yes
IDMT1:
Enabled
[ 038 125 ]
MAIN:
Protection active
306 001
MAIN:
Dynam. param. active
[ 040 090 ]
IDMT1:
Block. tIref,P> EXT
[ 038 114 ]
DIFF:
Inrush blk. 1 trigg.
[ 041 118 ]
DIFF:
Inrush blk. 2 trigg.
[ 041 119 ]
DIFF:
Inrush blk. 3 trigg.
[ 041 120 ]
IA,y
IB,y
IC,y
1.05 Iref
IDMT1:
Meas.value I/IN PSx
[ * ]
IDMT1:
Meas.value I/IN PSx
013 192
013 193
013 194
013 195
Fig. 3-121: Phase current stage.
The three phase currents are monitored by the P634 to detect when they exceed
the set thresholds. Alternatively, two different thresholds can be active. The
“dynamic” threshold is active for the set hold time of the “dynamic parameters”
(see Section 3.12.8, (p. 3-88)); the “normal” threshold is active when no hold
time is running.
3 Operation
P634
P634/EN M/R-42-A // P634‑311‑653 3-167