3.25.6 Warning Signal
64Z8918A
Parameter
set 1
set 2
set 3
set 4
THRM1:
Max.perm.cool.tmpPSx
081 080
082 080
083 080
084 080
THRM1:
Default CTA PSx
081 081
082 081
083 081
084 081
THRM1:
Rel. O/T warning PSx
081 079
082 079
083 079
084 079
THRM1:
Rel. O/T trip PSx
081 076
082 076
083 076
084 076
THRM1:
Hysteresis trip PSx
081 078
082 078
083 078
084 078
Parameter
set 1
set 2
set 3
set 4
THRM1:
Iref PSx
081 074
082 074
083 074
084 074
THRM1:
Start.fact.OL_RC PSx
081 075
082 075
083 075
084 075
THRM1:
Tim.const.1,>Ibl PSx
081 082
082 082
083 082
084 082
THRM1:
Tim.const.2,<Ibl PSx
081 083
082 083
083 083
084 083
THRM1:
Max.perm.obj.tmp.PSx
081 077
082 077
083 077
084 077
THRM1:
Warning pre-trip PSx
081 085
082 085
083 085
084 085
THRM1:
Pre-trip t. left,TH1
[ 004 153 ]
THRM1:
Coolant temp. TH1
[ 004 154 ]
THRM1:
Object temperat.,TH1
[ 004 151 ]
THRM1:
Status replica, TH1
[ 004 150 ]
THRM1:
Trip signal
[ 039 123 ]
THRM1:
Warning
[ 039 124 ]
THRM1:
Setting error,block.
[ 039 126 ]
THRM1:
Within pre-trip time
[ 039 153 ]
SFMON:
Setting error THRM1
[ 098 038 ]
MAIN:
Gen. trip command 1
[ 036 071 ]
THRM1:
Temp. offset repl. 1
[ 004 170 ]
THRM1:
Stat. repl., p.u.TH1
[ 004 204 ]
THRM1:
Object temp. p.u. 1
[ 004 205 ]
THRM1:
Coolant temp. p.u. 1
[ 004 206 ]
THRM1:
Starting k*Iref>
[ 039 151 ]
305 220
THRM1:
Tim.const.1,>Ibl PSx
[ * ]
THRM1:
Tim.const.2,<Ibl PSx
[ * ]
THRM1:
Max.perm.obj.tmp.PSx
[ * ]
THRM1:
Max.perm.cool.tmpPSx
[ * ]
THRM1:
Default CTA PSx
[ * ]
THRM1:
Rel. O/T warning PSx
[ * ]
THRM1:
Rel. O/T trip PSx
[ * ]
THRM1:
Hysteresis trip PSx
[ * ]
THRM1:
Warning pre-trip PSx
[ * ]
THRM1:
Operating mode
[ 039 121 ]
1: Absolute replica
2: Relative replica
1
2
< 0.1⋅Iref
I/Iref
THRM1:
Iref PSx
[ * ]
THRM1:
Start.fact.OL_RC PSx
[ * ]
kP⋅Iref
MAIN:
Protection active
306 001
THRM1:
I
THRM1:
Enabled
[ 039 129 ]
THRM1:
Block. by CTA error
305 221
Coolant temperature
THRM1:
Reset replica
[ 039 125 ]
THRM1:
With CTA
305 222
THRM1:
Replica block EXT
[ 039 150 ]
Fig. 3-132: Thermal overload protection.
A warning signal is issued when the thermal load reaches the warning level set at
THRM1: Rel. O/T warning PSx. Moreover, a time-to-tripping threshold (pre-
trip time) can be set. When the time left until tripping falls below the setting at
THRM1: Warning pre-trip PSx, a warning signal will be issued.
P634
3 Operation
3-180 P634/EN M/R-42-A // P634‑311‑653