3.23.2 Phase Current Stages
64Z8919A
DTOC1:
Enabled
[ 035 102 ]
MAIN:
Protection active
MAIN:
Dynam. param. active
[ 040 090 ]
&
IA,y
IB,y
IC,y
c
c
&
&
DTOC1:
I> dynamic PSx
[ * ]
DTOC1:
I> PSx
[ * ]
DTOC1:
Meas.value I/IN> PSx
[ * ]
c
c
&
&
DTOC1:
I>> dynamic PSx
[ * ]
DTOC1:
I>> PSx
[ * ]
DTOC1:
Meas.val. I/IN>> PSx
[ * ]
c
c
&
&
DTOC1:
I>>> dynamic PSx
[ * ]
DTOC1:
I>>> PSx
[ * ]
DTOC1:
Meas.val.I/IN>>> PSx
[ * ]
DTOC:
I> Starting A
DTOC:
I> Starting B
DTOC:
I> Starting C
DTOC:
I>> Starting A
DTOC:
I>> Starting B
DTOC:
I>> Starting C
DTOC:
I>>> Starting A
DTOC:
I>>> Starting B
DTOC:
I>>> Starting C
Parameter
set 1
set 2
set 3
set 4
DTOC1:
Meas.value I/IN> PSx
060 002
060 003
060 004
060 005
DTOC1:
I> PSx
076 051
077 051
078 051
079 051
DTOC1:
I> dynamic PSx
076 151
077 151
078 151
079 151
DTOC1:
Meas.val. I/IN>> PSx
060 006
060 007
060 008
060 009
DTOC1:
I>> PSx
076 052
077 052
078 052
079 052
DTOC1:
I>> dynamic PSx
076 152
077 152
078 152
079 152
Parameter
set 1
set 2
set 3
set 4
DTOC1:
Meas.val.I/IN>>> PSx
060 010
060 011
060 012
060 013
DTOC1:
I>>> PSx
076 053
077 053
078 053
079 053
DTOC1:
I>>> dynamic PSx
076 153
077 153
078 153
079 153
Fig. 3-108: Phase current stages, internal overcurrent startings.
The three phase currents are monitored by the P634 with three-stage functions
to detect when they exceed the set thresholds. One of two different threshold
types can be active. The “dynamic” thresholds are active for the set hold time for
the “dynamic parameters” (see Section 3.12.8, (p. 3-88)) and the “normal”
thresholds are active when no hold time is running.
There is also a separate setting for each overcurrent stage whether the starting
decision shall be based on the fundamental or on the r.m.s. value.
P634
3 Operation
3-154 P634/EN M/R-42-A // P634‑311‑653