5 Installation and Connection
WARNING
Sustained exposure to high humidity during storage may cause damage to
electronics and reduce the lifetime of the equipment.
We recommend that storage humidity shall not exceed 50% relative
humidity.
Once the device has been unpacked, we recommend that it is energized
within the three following months.
Where electrical equipment is being installed, sufficient time should be
allowed for acclimatization to the ambient temperature of the environment,
before energization.
WARNING
Only qualified personnel, familiar with the “Warning” page at the beginning of
this manual, may work on or operate this device.
WARNING
The instructions given in the Section 5.5, (p. 5-12) (“Protective and
Operational Grounding”) should be noted. In particular, check that the
protective ground connection is secured with a tooth lock washer, as per the
diagram “Installing the protective grounding conductor terminal” (Fig. 5-8,
(p. 5-12)).
If a cable screen is added to this connection or removed from it, then the
protective grounding should be checked again.
WARNING
The SC connector and RJ45 wire of the Ethernet module cannot be connected
at the same time.
P634
P634/EN M/R-42-A // P634311653 5-1