2.11 Recording Functions
2.11.1 Organization of the Recording Memories
Operating Data Memory
Scope for signals
●
All signals relating to normal operation; from a total of 1024 different logic
state signals.
Depth for signals
●
The 1000 most recent signals.
Monitoring Signal Memory
Scope for signals
●
All signals relevant for self-monitoring from a total of 1024 different logic
state signals.
Depth for signals
●
Up to 30 signals.
Overload Memory
Number
●
The 8 most recent overload events
Scope for signals
●
All signals relevant for an overload event from a total of 1024 different logic
state signals.
Depth for signals
●
200 entries per overload event.
Ground Fault Memory
Number
●
The 8 most recent ground fault events
Scope for signals
●
All signals relevant for a ground fault event from a total of 1024 different
logic state signals.
Depth for signals
●
200 entries per ground fault event.
Fault Memory
Number
●
The 8 most recent faults.
Scope for signals and fault values
●
All fault-relevant signals from a total of 1024 different logic state signals.
●
Sampled values for all measured currents and voltages
P634
2 Technical Data
2-22 P634/EN M/R-42-A // P634‑311‑653