2.3 Tests
2.3.1 Type Tests
Type Tests
All tests per EN 60255-26.
2.3.1.1 Electromagnetic Compatibility (EMC)
Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A.
1 MHz Burst Disturbance Test
Per EN 60255-22-1, Class III.
●
Common-mode test voltage: 2.5 kV.
●
Differential test voltage: 1.0 kV.
●
Test duration: > 2 s.
●
Source impedance: 200 Ω.
Immunity to Electrostatic Discharge
Per EN 60255-22-2 and IEC 60255-22-2, severity level 4.
Contact discharge
●
Single discharges: > 10.
●
Holding time: > 5 s.
●
Test voltage: 8 kV.
●
Test generator: 50 to 100 MΩ, 150 pF / 330 Ω.
Immunity to Radiated Electromagnetic Energy
Per EN 61000‑4‑3 and ENV 50204, severity level 3.
●
Antenna distance to tested device: > 1 m on all sides.
●
Test field strength, frequency band 80 to 1000 MHz: 10 V / m.
●
Test using AM: 1 kHz / 80 %.
●
Single test at 900 MHz: AM 200 Hz / 100%.
Electrical Fast Transient or Burst Requirements
Per EN 61000-4‑4 and IEC 60255‑22‑4, severity levels 3 and 4.
●
Rise time of one pulse: 5 ns.
●
Impulse duration (50% value): 50 ns.
●
Amplitude: 2 kV / 1 kV or 4 kV / 2 kV.
●
Burst duration:15 ms.
●
Burst period: 300 ms.
●
Burst frequency: 5 kHz.
●
Source impedance: 50 Ω.
Power Frequency Immunity
Per IEC 60255‑22‑7, Class A:
P634
2 Technical Data
2-4 P634/EN M/R-42-A // P634‑311‑653