EasyManua.ls Logo

Micom P634 - Page 31

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication interface IEC 61850
●
Fiber (X7, X8)
o
optical fiber connection BFOC-ST
®
connector 2.5 per IEC 60874‑10 (for
glass fibers).
(ST
®
is a registered trademark of AT&T Lightguide Cable Connectors.)
●
Fiber (X13)
o
SC connector per IEC 60874‑14‑4 (for glass fibers)
●
Wire leads (X12)
o
RJ45 connector per ISO/IEC 8877.
Current measuring inputs (conventional inputs)
●
Threaded terminal ends, pin-type cable lugs: M5, self-centering with cage
clamp to protect conductor cross-sections ≤ 4 mm² (US: AWG12), or
●
Threaded terminal, ring-terminal connection: M4.
Other inputs and outputs
●
Threaded terminal ends, pin-type cable lugs: M3, self-centering with cage
clamp to protect conductor cross-sections 0.2 to 2.5 mm² (US: AWG25 to
AWG14), or
●
Threaded terminal ends, ring-type cable lugs: M4.
Creepage Distances and Clearances
●
Per EN 60255-27.
●
Pollution degree 3, working voltage 250 V,
●
overvoltage category III, impulse test voltage 5 kV.
2 Technical Data P634
P634/EN M/R-42-A // P634‑311‑653 2-3