60/(set cycle time) comes to an integer. In all other cases the counter values are
transmitted at time intervals determined by a free running internal clock.
3.36.5 Counter Values Reset
19Z82ANA
1: execute
MAIN:
General reset EXT
[ 005 255 ]
COUNT:
Reset
[ 217 005 ]
MAIN:
General reset USER
[ 003 002 ]
COUNT:
Reset EXT
[ 217 004 ]
0
1
0: don't execute
1: execute
COUNT:
Reset USER
[ 217 003 ]
COUNT:
Transmit counts EXT
[ 217 009 ]
COUNT:
Set counter 1 EXT
[ 217 130 ]
1: Yes (= on)
MAIN:
Device on-line
[ 003 030 ]
Debouncing
0
1
0: No
1: Yes
COUNT:
General enable USER
[ 217 000 ]
COUNT:
Count 1
[ 217 100 ]
COUNT:
Transmit counts USER
[ 217 008 ]
m
CT=m
+
R
COUNT:
Cycle t.count transm
[ 217 007 ]
C
G
= 0 min
C
COMM1:
Count 1
[ --- --- ]
COUNT:
Count 1
[ 217 100 ]
COUNT:
Transmit counts
[ 217 010 ]
COUNT:
Enabled
[ 217 001 ]
0
1
0: don't execute
1: execute
1
COUNT:
Debounce t. count. 1
[ 217 160 ]
Fig. 3-184: Binary Count. (This diagram shows counter 1 as an example. The displayed logic is also valid for
counters 2 to 4, where COUNT: Set counter 1 EXT and COUNT: Count 1 have to be replaced by the
respective parameters.
The counter values may be reset – all at once – by setting parameter
COUNT: Reset USER or via an appropriately configured binary signal input as
well as by the general reset action.
P634
3 Operation
3-228 P634/EN M/R-42-A // P634‑311‑653