Q9Z5021A
LIMIT:
Enabled
[ 040 074 ]
LIMIT:
Starting IDC,lin>
[ 040 180 ]
LIMIT:
tIDC,lin> elapsed
[ 040 182 ]
LIMIT:
Starting IDC,lin>>
[ 040 181 ]
LIMIT:
tIDC,lin>> elapsed
[ 040 183 ]
LIMIT:
Starting IDC,lin<
[ 040 184 ]
LIMIT:
tIDC,lin< elapsed
[ 040 186 ]
LIMIT:
Starting IDC,lin<<
[ 040 185 ]
LIMIT:
tIDC,lin<< elapsed
[ 040 187 ]
0
0: No
1: Yes
LIMIT:
General enable USER
[ 014 010 ]
1
LIMIT:
IDC,lin>
[ 014 110 ]
LIMIT:
IDC,lin>>
[ 014 111 ]
LIMIT:
tIDC,lin>
[ 014 112 ]
LIMIT:
tIDC,lin>>
[ 014 113 ]
LIMIT:
IDC,lin<
[ 014 114 ]
LIMIT:
IDC,lin<<
[ 014 115 ]
LIMIT:
tIDC,lin<
[ 014 116 ]
LIMIT:
tIDC,lin<<
[ 014 117 ]
MAIN:
Protection active
306 001
MEASI:
Curr. IDC,lin. p.u.
[ 004 136 ]
t 0
c
t 0
c
t 0
c
t 0
c
Fig. 3-169: Monitoring the linearized measured DC values
3.32.3 Monitoring the Measured Temperature Value
The temperature that is measured by the P634 using a resistance thermometer
is monitored by two stages to determine if it exceeds or falls below set
thresholds. If it exceeds or falls below the thresholds, a signal is issued once a
set time-delay has elapsed.
P634
3 Operation
3-214 P634/EN M/R-42-A // P634311653