Phase-to-phase
RMS value 150 V.
Coupling resistance 100 Ω.
Coupling capacitor 0.1 μF, for 10 s.
Phase-to-ground
RMS value 300 V.
Coupling resistance 220 Ω.
Coupling capacitor 0.47 μF, for 10 s.
To comply with this standard, it is suggested to set the parameter (010 220)
INP: Filter to 6 [steps].
Current/Voltage Surge Immunity Test
Per EN 61000-45 and EN 60255-225, insulation class 4.
Testing of circuits for power supply and asymmetrical or symmetrical
lines.
Open-circuit voltage, front time / time to half-value: 1.2 / 50 µs.
Short-circuit current, front time / time to half-value: 8 / 20 µs.
Amplitude: 4 / 2 kV.
Pulse frequency: > 5 / min.
Source impedance: 12 / 42 Ω.
Immunity to Conducted Disturbances Induced by Radio Frequency Fields
Per EN 61000-4-6 and EN 60255-226, severity level 3.
Test voltage: 10 V.
Power Frequency Magnetic Field Immunity
Per EN 61000-4-8 or IEC 61000-4-8, severity level 4.
Test frequency: 50 Hz
Test field strength: 30 A / m.
Alternating Component (Ripple) in DC Auxiliary Energizing Quantity
Per EN 60255-11.
12 %.
2.3.1.2 Insulation
Voltage Test
Per EN 60255-27.
2 kV AC, 60 s
Only direct voltage (2.8 kV DC) must be used for the voltage test on the power
supply inputs. The PC interface must not be subjected to the voltage test.
Impulse Voltage Withstand Test
Per EN 60255-27.
Front time: 1.2 µs
Time to half-value: 50 µs
Peak value: 5 kV
Source impedance: 500 Ω
2 Technical Data
P634
P634/EN M/R-42-A // P634311653 2-5

Table of Contents