WARNING
When using the programmable logic, the user must carry out a functional
type test to conform with the requirements of the relevant protection/control
application. In particular, it is necessary to verify that the requirements for
the implementation of logic linking (by setting) as well as the time
performance during startup of the P634, during operation and when there is a
fault (blocking of the P634) are fulfilled.
0: No
0
1
LOGIC:
Set 1 USER
[ 034 030 ]
1: Yes
LOGIC:
1 has been set
[ 034 067 ]
LOGIC:
1 set externally
[ 034 075 ]
INP:
Fct. assignm. U xxx
[ xxx xxx ]
Address 036 051
U x1
U x2
U x3
U xx
Address 036 059
LOGIC:
Set 1 EXT
[ 034 051 ]
LOGIC:
Reset 1 EXT
[ 034 059 ]
D5Z52FAB
Fig. 3-174: Control of logic operations via setting parameters or stored input signals. (The logic does not apply to
LOG_2.)
The LOGIC: Trigger 1 signal is a “triggering function” that causes a 100 ms
pulse to be issued.