Parameter Address
Default Min Max Unit Logic Diagram
Main function
MAIN: Chann.assign.COMM1/2
003 169
1: COMM1->chann.1,(2-2) Fig. 3-67, (p. 3-98)
[spacer]
Assignment of communication interfaces to physical communication channels.
[spacer]
MAIN: Prim.Source TimeSync
103 210
0: COMM1/IEC
[spacer]
Selection of the primary source for date and time synchronization. Available are
COMM1/IEC, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
[spacer]
MAIN: BackupSourceTimeSync
103 211
1: COMM2/PC
[spacer]
Selection of the backup source for date and time synchronization. Available are
COMM1/IEC, COMM2/PC, IRIG-B or a binary input for minute signal pulses. The
backup source is used when there is no synchronization generated by the
primary source after MAIN: Time sync. time-out has elapsed.
[spacer]
MAIN: Time sync. time-out
103 212
Blocked 1 60 min
[spacer]
Time-out setting for the time synchronization generated by the primary source.