Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
REF_3: Ref. curr. Iref
019 036
Not measured 0.000 50.000 kA
[spacer]
Display of the reference current calculated by the P634.
[spacer]
REF_1: Match. fact. kam,N,a
004 160
Not measured 0.000 50.000 Fig. 3-100, (p. 3-144)
[spacer]
REF_1: Match. fact. kam,N,b
019 123
Not measured 0.000 50.000
[spacer]
REF_1: Match. fact. kam,N,c
019 124
Not measured 0.000 50.000
[spacer]
REF_1: Match. fact. kam,N,d
019 125
Not measured 0.000 50.000
[spacer]
REF_3: Matching fact. kam,N
004 162
Not measured 0.000 50.000
[spacer]
Display of the matching factor calculated by the P634.
[spacer]
REF_1: Matching fact. kam,Y
004 163
Not measured 0.000 50.000 Fig. 3-100, (p. 3-144)
[spacer]
REF_2: Matching fact. kam,Y
004 164
Not measured 0.000 50.000
[spacer]
REF_3: Matching fact. kam,Y
004 165
Not measured 0.000 50.000
[spacer]
Display of the matching factor calculated by the P634 for the neutral-point
current.
[spacer]
REF_1: Meas. value rel. Id
011 039
0.00 0.00 0.20 Iref Fig. 3-104, (p. 3-149)
[spacer]
REF_2: Meas. value rel. Id
011 044
0.00 0.00 0.20 Iref
[spacer]
REF_3: Meas. value rel. Id
011 045
0.00 0.00 0.20 Iref
[spacer]
Setting for the minimum differential current that must be exceeded in order for
the P634 to display the differential currents as measured operating data.
[spacer]
REF_1: Meas. value rel. IR
011 040
0.00 0.00 0.20 Iref Fig. 3-104, (p. 3-149)
[spacer]
REF_2: Meas. value rel. IR
011 046
0.00 0.00 0.20 Iref
P634 7 Settings
7-88 P634/EN M/R-42-A // P634‑311‑653