EasyManua.ls Logo

Micom P634 - Page 452

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
CBF_4: Delay/starting trig.
022 247
0.00 0.00 100.00 s
[spacer]
The signal CBF_1: Trip signal (or CBF_2: Trip signal, ..., resp.) is
issued when this timer stage's time duration has elapsed.
[spacer]
CBF_1: Delay/fault beh. CB
022 171
0.12 0.00 100.00 s Fig. 3-167, (p. 3-212)
[spacer]
CBF_2: Delay/fault beh. CB
022 227
0.12 0.00 100.00 s
[spacer]
CBF_3: Delay/fault beh. CB
022 240
0.12 0.00 100.00 s
[spacer]
CBF_4: Delay/fault beh. CB
022 254
0.12 0.00 100.00 s
[spacer]
If during this delay time period the circuit breaker does not provide a signal from
its auxiliary contacts that it is closed, then faults behind the CB are recognized
through the current criterion (see section “Fault behind CB protection”).
[spacer]
CBF_1: Delay/CB sync.superv
022 172
Blocked 0.00 100.00 s Fig. 3-168, (p. 3-212)
[spacer]
CBF_2: Delay/CB sync.superv
022 218
Blocked 0.00 100.00 s
[spacer]
CBF_3: Delay/CB sync.superv
022 241
Blocked 0.00 100.00 s
[spacer]
CBF_4: Delay/CB sync.superv
022 255
Blocked 0.00 100.00 s
[spacer]
Setting for the time delay to bridge circuit breaker operate times during CB
synchronization supervision.
P634 7 Settings
7-98 P634/EN M/R-42-A // P634311653

Table of Contents

Related product manuals