Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
COUNT: Limit counter 4
217 224
Blocked 1 65000
[spacer]
Setting a limit for the counter value. A warning signal is issued if the counter
value exceeds the set limit. Setting this parameter to Blocked disables the limit
check.
[spacer]
COUNT: Cycle t.count transm
217 007
0: No transmission Fig. 3-184, (p. 3-228)
[spacer]
Setting the cycle time for the periodic transmission of the counts.
[spacer]
COUNT: IEC61850 pulsQty
221 096
1 0 1000
[spacer]
Setting the scaling factor to transmit the counter value via IEC 61850. According
to the standard the resulting value is calculated as:
Value transmitted = actual value · pulsQty
(see IEC 61850: Value = actVal · pulsQty).
7 Settings P634
P634/EN M/R-42-A // P634311653 7-149