Parameter Address
[spacer]
SFMON: Wrong module slot 10
096 109
[spacer]
SFMON: Wrong module slot 11
096 110
[spacer]
SFMON: Wrong module slot 12
096 111
[spacer]
SFMON: Wrong module slot 13
096 112
[spacer]
SFMON: Wrong module slot 14
096 113
[spacer]
SFMON: Wrong module slot 15
096 114
[spacer]
SFMON: Wrong module slot 16
096 115
[spacer]
SFMON: Wrong module slot 17
096 116
[spacer]
SFMON: Wrong module slot 18
096 117
[spacer]
SFMON: Wrong module slot 19
096 118
[spacer]
SFMON: Wrong module slot 20
096 119
[spacer]
SFMON: Wrong module slot 21
096 120
[spacer]
Module in wrong slot.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer]
SFMON: Wrong module Dig.Bus
096 123
[spacer]
The device has been fitted with a wrong digital bus. Since this is checked using
the module variant number this signal can also occur after a firmware upgrade
to a version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer]
SFMON: Wrong module HMI
096 124
[spacer]
The device has been fitted with a wrong HMI. Since this is checked using the
module variant number this signal can also occur after a firmware upgrade to a
version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
11 Troubleshooting P634
P634/EN M/R-42-A // P634‑311‑653 11-5