EasyManua.ls Logo

Micom P634 - Page 739

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Address
[spacer]
SFMON: Wrong module slot 10
096 109
[spacer]
SFMON: Wrong module slot 11
096 110
[spacer]
SFMON: Wrong module slot 12
096 111
[spacer]
SFMON: Wrong module slot 13
096 112
[spacer]
SFMON: Wrong module slot 14
096 113
[spacer]
SFMON: Wrong module slot 15
096 114
[spacer]
SFMON: Wrong module slot 16
096 115
[spacer]
SFMON: Wrong module slot 17
096 116
[spacer]
SFMON: Wrong module slot 18
096 117
[spacer]
SFMON: Wrong module slot 19
096 118
[spacer]
SFMON: Wrong module slot 20
096 119
[spacer]
SFMON: Wrong module slot 21
096 120
[spacer]
Module in wrong slot.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer]
SFMON: Wrong module Dig.Bus
096 123
[spacer]
The device has been fitted with a wrong digital bus. Since this is checked using
the module variant number this signal can also occur after a firmware upgrade
to a version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer]
SFMON: Wrong module HMI
096 124
[spacer]
The device has been fitted with a wrong HMI. Since this is checked using the
module variant number this signal can also occur after a firmware upgrade to a
version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
11 Troubleshooting P634
P634/EN M/R-42-A // P634311653 11-5

Table of Contents

Related product manuals