Parameter Address
[spacer]
SFMON: Inval. SW vers.comm.
093 075
[spacer]
Incorrect or invalid communication software has been downloaded.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer]
SFMON: Inval. Config. IEC
093 079
[spacer]
Invalid parameters in the IEC configuration.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer]
SFMON: Invalid SW vers. Y
093 113
[spacer]
Incorrect or invalid software for analog I/O module Y has been downloaded.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer]
SFMON: Time-out module Y
093 112
[spacer]
Watchdog is monitoring the periodic status signal of the analog I/O module Y. It
has detected an error.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer]
SFMON: M.c.b. trip V
098 000
[spacer]
The line-side voltage transformer m.c.b. has tripped.
Device reaction: Blocking of the short-circuit direction determination.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer]
SFMON: Insulation Alarm 1
098 091
[spacer]
SFMON: Insulation Alarm 2
098 092
[spacer]
SFMON: Insulation Alarm 3
098 093
[spacer]
SFMON: Buchholz Alarm 1
098 094
[spacer]
SFMON: Buchholz Alarm 2
098 095
[spacer]
SFMON: Buchholz Alarm 3
098 096
[spacer]
The transformer monitoring has received/detected a Buchholz/insulation fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
11 Troubleshooting P634
P634/EN M/R-42-A // P634‑311‑653 11-11