[✓] <45> = Single command C_SC_NA_1
[✓] <46> = Double command C_DC_NA_1
[✓] <47> = Regulating step command C_IT_NA_1
[ ] <48> = Set point command, normalized value C_RC_NA_1
[ ] <49> = Set point command, scaled value C_SE_NB_1
[ ] <50> = Set point command, short floating point value C_SE_NC_1
[ ] <51> = Bit string of 32 bit C_BO_NA_1
System Information in Monitor Direction (Station-Specific Parameter)
[✓] <70> = End of initialization ME_EI_NA_1
System Information in Control Direction (Station-Specific Parameter)
[✓] <100> = Interrogation command C_IC_NA_1
[✓] <101> = Counter interrogation command C_CI_NA_1
[✓] <102> = Read command C_RD_NA_1
[✓] <103> = Clock synchronization command C_CS_NA_1
[✓] <104> = Test command C_TS_NB_1
[ ] <105> = Reset process command C_RP_NC_1
[ ] <106> = Delay acquisition command
(See National Preface of EN 60870-5-101.)
C_CD_NA_1
Parameter in Control Direction (Station-Specific Parameter)
[✓] <110> = Parameter of measured value, normalized value P_ME_NA_1
[✓] <111> = Parameter of measured value, scaled value P_ME_NB_1
[ ] <112> = Parameter of measured value, short floating point value P_ME_NC_1
[ ] <113> = Parameter activation P_AC_NA_1
File Transfer (Station-Specific Parameter)
P634
A4 Telecontrol Interfaces
A4-6 P634/EN M/R-42-A // P634‑311‑653