A4.2.1.3.4 Selection of Standard Information Numbers in Control Direction
System Functions in Control Direction
INF Description
[] <0> Initiation of general interrogation
[] <0> Time synchronization
General Commands in Control Direction
INF Description P634 Designations
(Address) Description
[] <16> Auto-recloser on/off
[] <17> Teleprotection on/off
[] <18> Protection on/off (003 030) MAIN: Device on-line
[] <19> LED reset (021 010) MAIN: Reset indicat. USER
[] <23> Activate characteristic 1
(Switches
PSS: Param.subs.sel.
USER to Parameter subset
1.)
(003 060) PSS: Param.subs.sel. USER
[] <24> Activate characteristic 2
(Switches
PSS: Param.subs.sel.
USER to Parameter subset
2.)
(003 060) PSS: Param.subs.sel. USER
[] <25> Activate characteristic 3
(Switches
PSS: Param.subs.sel.
USER to Parameter subset
3.)
(003 060) PSS: Param.subs.sel. USER
[] <26> Activate characteristic 4
(Switches
PSS: Param.subs.sel.
USER to Parameter subset
4.)
(003 060) PSS: Param.subs.sel. USER