Loading...
Version Changes
Note:
This version is not released for applications with IEC
61850 systems! Version 610-714 may be used as an
alternative.
COMM1 The upgraded communications software 3.18 is now
implemented. Various small bugs have been fixed in
communication protocols per IEC 60870-5-101 and
MODBUS.
P634
  ‑305
  ‑403/404
  ‑610-713
Release: 2006-12-12
Hardware
No changes.
Diagram
No changes.
Software
Note:
This version is not released for applications with IEC
61850 systems! Version 610-714 may be used as an
alternative.
MAIN
Bug fixing:
The sequence of MAIN: General starting (036
000) and DIFF: Trip signal (041 075) have
been changed such that starting always comes
first.
P634
  ‑305
  ‑403/404
  ‑610-714
Release: 2007-02-07
Hardware
No changes.
Diagram
No changes.
Software
IEC
Bug fixing:
Previously a break in the client-server
communications link could occur after
approximately 49 days for about 20 minutes.
GOOSE and GSSE are not affected.
P634
  ‑306
  ‑405/406
  ‑611
Release: 2007-03-15
Hardware
A5 P634 Version History P634