2 - 12
2.2 Applicable Modules
2.2.2 Precautions when using I/O modules or intelligent function modules
2
SYSTEM CONFIGURATION
(c) Precautions for using CC-Link module
Note that there are restrictions on the following functions of the CC-Link module
controlled by the C Controller module.
The CC-Link dedicated instructions are not executable.
Interrupt sequence program start is not applicable.
The automatic CC-Link start is not applicable.
The standby master function is not applicable.
The remote I/O network mode is not applicable.
(d) Precautions for using MELSECNET/H module
Note that there are restrictions on the following functions of the MELSECNET/H
module controlled by the C Controller module.
Not applicable to the remote I/O network.
Applicable to only the PLC-to-PLC network.
Not applicable as a relay station of the data link transfer function or routing
function.
When using the data link transfer function or routing function, use the
MELSECNET/H module controlled by programmable controller CPU as a
relay station.
The link dedicated instructions of MELSECNET/H are not applicable.
Note that the message communication function equivalent to the SEND/
RECV instruction is provided. ( Section 4.4)
Interrupt sequence program start is not applicable.
The network diagnostics (test) function is not provided.
The simple dual-structure network function is not applicable.
(The network type cannot be set to "MNET/H standby station".)
System-specified access is not available for other station access to a
redundant CPU. Only host system access (station No.-specified access) is
available.
The mode cannot be set to the "Debug mode".
(e) Precautions for using serial communication module
The serial communication module controlled by the C Controller module supports
only communication based on the nonprocedural protocol.
1) Note that the following functions are not applicable:
The MC protocol and bidirectional protocol.
The instructions dedicated to the serial communication module.
Programmable controller CPU monitoring function.
The modem function.
2) Make the following setting when using an interrupt program.
Set the interrupt event No. on the <<System setting>> tab of the C
Controller setting utility.
Write "1" into the buffer memory (address 2010H/2110H) of the serial
communication module.
In the user program, create a program to receive an interrupt event and
execute the relevant processing using the QBF_WaitUnitEvent function.