F1: Program Mode
5-27
5
VALVE LIMIT TIMER (Range: 1.0 - 6.0 Minutes) - This timer starts whenever the con-
troller attempts to move the car down, and is reset when the car reaches its destination floor. If
the timer expires before the car reaches its destination, the controller will stop trying to move
the car, in order to protect the valves. The Motor/Valve Limit Timer Indicator on the HC-MPU
board will turn ON.
DOOR HOLD INPUT TIMER (Range: 0-240 Seconds) - This timer will be used only if
there is a DHLD (Door Hold) input on the controller (see “Spare Inputs Menu Options” on
page 5-29). Usually, a Door Hold button will be connected to this input. This timer determines
the amount of time that the doors will stay open when the door hold open button is pressed. The
timer will be canceled and the doors will begin to close, if either the Door Close button or a Car
Call button is pressed. If a Door Hold Key switch (instead of a button) is connected to the DHLD
input, this timer value should be set to 0, so that the doors will close when the switch is turned
to the OFF position.
PARKING DELAY TIMER (Range: 0.0-6.0 Minutes) - This timer is used only if a park-
ing floor is selected (see “PARKING FLOOR” on page 5-19 and see “ALT. PARKING FLOOR” on
page 5-19). The timer starts when the car is free of call demand. The car will not park until the
timer elapses.
FAN/LIGHT OUTPUT TIMER (Range: 5.0-20.0 Minutes) - Used with the FLO out-
put. This timer sets the amount of time that will pass before the FLO output will be activated.
The time will start when the car becomes inactive. The FLO output should be connected to a
relay that when activated, will turn OFF the fan and light within the car. This output is also used
for PI Turned Off if No Demand (see “PI TURNED OFF IF NO DEMAND?” on page 5-50).
HOSPITAL EMERG. TIMER (Range: 1.0-10.0 Minutes) - Used when the HOSPITAL
EMERG. OPERATION option is set to YES. This timer sets the amount of time that the car will
remain at the hospital emergency floor with the doors open before automatically returning to
normal service (see “HOSPITAL EMERG. OPERATION?” on page 5-50).
DOOR OPEN PROTECTION TIMER (Range 8 - 30 Seconds) - This timer determines
how long the door operator will attempt to open the doors. If DOL does not go low within this
time, the doors will then begin to close.
CTL DOOR OPEN TIMER (Range: 2.0 - 60.0 seconds) - Used when either CTL or CTF
spare inputs are programmed. This timer is used to indicate how long the doors should remain
open after lowering to the lobby floor when the CTL or CTF spare input is activated.
DOOR BUZZER TIMER (Range: 0 - 30 Seconds) - This timer determines the length of
time the door buzzer sounds before the doors are automatically closed.
OPN/CLS INTRLOCK TIMER (Range: 050ms - 950ms, 50ms increments) Intro-
duces a delay when closing or opening doors are abruptly reversed (i.e., photo eye activation,
door button press, etc.). This may be required if the door operator is sensitive to such reversal
due to de-bounce capability. Set to NONE if unnecessary.
FIRE PH1 RECLOSE TIMER (Range: None or 1 - 120 seconds) - If set to a value other
than NONE, the doors will close after the set number of seconds following a Fire Service Phase 1
recall. Doors may be opened using in-car or hall door open buttons.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motion Control Engineering 2000 and is the answer not in the manual?

Motion Control Engineering 2000 Specifications

General IconGeneral
BrandMotion Control Engineering
Model2000
CategoryController
LanguageEnglish

Related product manuals