Troubleshooting
6-56 Manual # 42-02-1P21
HC-UIO-2 Switches 7, 8 and 9 Settings
On the HC-UIO-2 Board switches 7 and 8 set the baud rate at which the CAN bus communicates
with this board.
On the HC-UIO-2 Board switch 9 sets the activation threshold for inputs IO1 through IO16..
HC-UIO-2 Used for Calls
When HC-UIO-2 boards are used for hall or car calls, the brightness of the LEDs associated
with inputs and outputs has significance.
Level o - LED Off
The input is not active and the output is not latched on.
Level 1 - LED medium brightness
The input is not active and the output is latched on.
Level 2 - LED full brightness
The input is active and the output may or may not be latched on.
LED flashing
Maximum continuous current draw exceeded (overload or short detected).
Hospital Emergency Operation I/O
I/O 1 through I/O 4 on UIO-2 Board #16 are used for hospital emergency operation connections
HEO, HWI, HSEL, and HOSPH2 respectively.
Table 6.17 HC-UIO-2 Board Switches 7 and 8
Sw 7 Sw 8 Baud Rate Description
OFF OFF 500 kbps For boards inside the controller, RJ12 cable from J2 on HC-UIO board to
HC-CHP board Internal Network J1 through J10.
ON OFF 250 kbps For boards on the cartop, RJ12 cable from J2 on HC-UIO board to MC-LSI
board LAN connectors. Caution: Do not connect to J3 on the MC-LSI
(Landing System) board.
OFF ON 125 kbps Future use
Table 6.18 HC-UIO-2 Board Switch 9 for I/O Boards
Sw 9 Description
OFF Sets Input activation threshold to 18 Volts ac or dc
ON Sets Input activation threshold to 55 to 65 Volts ac or dc
Table 6.19 HC-UIO-2 Board Switch 9 for Call Boards
Sw 9 Description
OFF Sets Input activation threshold to 0.6 Volts ac or dc
ON Sets Input activation threshold to 0.2 Volts ac or dc