2-1-3
Function Specifications
The function specifications of the NX-series EtherNet/IP Unit are given below.
Item NX-EIP201
Communica-
tions
EtherNet/I
P port
Communications protocol TCP/IP or UDP/IP
CIP communications
services
Tag data links Programless cyclic data exchange
is performed with the devices on
the EtherNet/IP network.
Message Com-
munications
CIP commands are sent to or re-
ceived from the devices on the
EtherNet/IP network.
TCP/IP application SNMP agent EtherNet/IP port internal status in-
formation is provided to network
management software that uses an
SNMP manager
.
System
manage-
ment
Event logs Function Events are recorded in the logs.
Maximum number of
events
System event
log
1,024
Access event
log
512
User-defined
event log
None
2 Specifications and Application Procedures
2-5
NX-series EtherNet/IP Unit User's Manual (W627)