A-2
Functional Comparison of EtherNet/IP
Ports on NJ/NX-series CPU Units and
Other Series
OK: Supported, ---: Not supported
Item
Built-in
Ether-
Net/IP
port on
NX701
CPU
Unit
Built-in
Ether-
Net/IP
port on
NX502
CPU
Unit
Built-in
Ether-
Net/IP
port on
NX102
CPU
Unit
Built-in
Ether-
Net/IP
port on
NX1P2
CPU
Unit
Built-in
Ether-
Net/IP
port on
NJ-ser-
ies
CPU
Unit
NX-ser-
ies
Ether-
Net/IP
Unit
CJ-ser-
ies
Ether-
net
Unit
EtherNet/IP Unit (built-in
port on CJ2 CPU Unit)
Unit
version
1.0
Unit
version
2.0
Unit
version
2.1
Tag data link com-
munications serv-
ice
OK OK OK OK OK OK
---
OK OK OK
CIP message
communications
service
OK OK OK OK OK OK
---
OK OK OK
IP routing
OK OK OK
--- ---
OK
--- --- --- ---
Socket service
OK OK OK OK OK
---
OK
--- --- ---
FTP server
OK OK OK OK OK
---
OK
---
OK OK
FTP client
OK OK OK OK OK
--- --- --- --- ---
Mail send/receive --- --- --- --- --- ---
OK
--- --- ---
Web functions --- --- --- --- --- ---
OK
--- --- ---
Automatic adjust-
ment of PLC/
Controller
s inter-
nal clock
OK OK OK OK OK
---
OK
---
OK OK
Error history
OK
*1
OK
*1
OK
*1
OK
*1
OK
*1
OK
*1
OK OK OK OK
Response to
PING command
OK OK OK OK OK OK OK OK OK OK
SNMP/SNMP trap
OK OK OK OK OK OK
--- ---
OK OK
CIDR function for
IP addresses
OK OK OK OK OK OK
--- ---
OK OK
DHCP client ---
OK
--- --- --- --- --- --- --- ---
Online connection
via EtherNet/IP
using CX-One
--- --- --- --- --- ---
OK
---
OK OK
Online connection
via EtherNet/IP
using Network
Configurator
OK OK OK OK OK OK
---
OK OK OK
Mounting in an
NJ-series CPU
Unit
--- --- --- --- --- --- --- --- ---
OK
*2
Appendices
A-4
NX-series EtherNet/IP Unit User's Manual (W627)