8-4-4
Settings for Devices That Access the Controller
This section shows the set values of Packet Filter for each device that accesses the Controller.
Settings for Connecting Sysmac Studio
The following table shows the setting values for the destination port of Packet Filter when the Sysmac
Studio is connected.
Connection
type
*1
Destination port settings
Protocol
Destination Port
Specification Meth-
od
Destination Port
Range Specifica-
tion
Destination
Port
Start Number
Destination
Port
End Number
Ethernet connec-
tion via a hub
tcp Port specification No check. 443 ---
*1. Select Controller – Communications Setup – Connection type
on the Sysmac Studio to make this set-
ting.
Settings for Connecting Support Software Other Than Sysmac Stu-
dio
The settings for connecting the Support Software other than Sysmac Studio are as follows.
Support
Software
Connection
type
Destination port settings
Protocol
Destination
Port
Specification
Method
Destination
Port
Range Speci-
fication
Destination
Port
Start Num-
ber
Destination
Port
End Num-
ber
Network
Configura-
tor for
EtherNet/I
P
Ethernet I/F tcpSettings for
Connecting Sup-
port Software
Other Than Sys-
mac Studio on
page 8-
17
Port specifica-
tion
No check.
44818 ---
udp
*1
Port specifica-
tion
No check. 44818 ---
icmpSettings for
Connecting Sup-
port Software
Other Than Sys-
mac Studio on
page
8-17
--- --- --- ---
Sysmac
Conrtoller
Log Up-
load Tool
Ethernet
connection
via a hub
Same settings as for Sysmac Studio. Refer to
Settings for Connecting Sysmac
Studio on page 8-17 for settings for the Sysmac Studio.
Allow tcp: 443 for the destination port.
*1. When filtering by IP address is used, allow the following IP addresses.
Source IP address: Computer’
s IP address, Destination IP address: Local broadcast to the computer’s net-
work (When the computer’s IP address is 192.168.250.100/24, allow 192.168.250.255.)
8 TCP/IP Functions
8-17
NX-series EtherNet/IP Unit User's Manual (W627)
8-4 Packet Filter
8
8-4-4 Settings for Devices That Access the Controller