Parker EME
Compax3 device description
192-120114 N5 C3I22T11 June 2008 85
Description
In this chapter you can read about:
Basic functions:.................................................................................................................. 85
Access to the hazardous area ........................................................................................... 85
Basic functions:
Compax3 devices disabled by:
Channel 1: Energize deactivated by PLC due to open contacts of the Emergency
power-off module (13 -14)
Channel 2: Enable input to "0" through open contacts of Emergency power-off mo-
dule (57 - 58)
Activate Emergency power-off module
Before the Compax3 can be placed in operation, the Emergency Power-off module
must be activated by a pulse to Input S33/S34.
Prerequisite:
S3 closed
Safety door closed: only in this case the safety door monitor enables the emer-
gency power off module via two channels
K1 energized via PLC (feedback channel 1: motor not energized)
The feedback contact of all Compax3 devices must be closed (channel 2).
If S33 & S34 of the Emergency power-off module are briefly connected (pulse) the
contacts will be closed (between 13 & 14 and between 57 & 58).
Energize Compax3 (Motor and power output stage)
The PLC enables the Compax3 devices by means of the control word and the
Emergency power-off module enables the Compax3 devices by means of the
Enable input. (if an error is still pending on Compax3, it must be previously
acknowledged/reset)
The motors are energized with current.
Summary: Compax3 is only energized if the feedback functions are capable of
functioning via two channels.
Access to the hazardous area
Activate Emergency power-off switch
The two-channel disconnecting at the emergency power-off switch deactivates the
emergency power-off module – the contacts 13 – 14 will open immediately.
The PLC evaluates this and responds as follows:
Channel 1: The Compax3 devices receive via the control word the command to
guide the drive to currentless state (vi the ramp for "deenergizing" configured in the
C3 ServoManager).
Channel 1 feedback: The Compax3 feedback via the status word is evaluated by
the PLC and passed on to the emergency power-off module via K1.
Channel 2:After the delay time set in the Emergency power-off module, (this time
must be set so that all drives are stopped after it has elapsed) the contacts betwe-
en 57 & 58 open, which in turn deactivates the Enable inputs of the Compax3 devi-
ces.
Channel 2 feedback:Via the series circuit of all feedback contacts, the ”Safe
Standstill” status (all Compax3 devices without current) is reported.
Only if the drives are all at a standstill, the safety door may be opened and the
hazardous area may be accessed.

Table of Contents

Other manuals for Parker Compax3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker Compax3 Series and is the answer not in the manual?

Parker Compax3 Series Specifications

General IconGeneral
Enclosure RatingIP20
Control ModesSpeed, Torque, Position
Communication InterfacesCANopen, EtherCAT
Feedback OptionsIncremental Encoder, Resolver
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Cooling MethodForced Air, Natural Convection
Relative Humidity5 to 85 %, non-condensing
Operating Temperature0 to +45 °C (derating may apply above 40°C)