7.4 Faults
284 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Code Name Causes Possible Solutions
Uv2 Control Power Undervoltage
The value set in L2-02 [RideThrough Time@Power
Loss] increased and the momentary power loss
recovery unit is not connected to the drive.
Connect the momentary power loss recovery unit to the drive.
There was a problem with the drive hardware. Re-energize the drive.
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact the
manufacturer or your nearest sales representative.
Note:
The drive detects this error if the control power supply voltage decreases.
Do a Fault Reset to clear the fault.
Fault trace is not available for this fault.
Code Name Causes Possible Solutions
Uv3 Soft Charge Answerback Fault
The relay or contactor on the soft-charge bypass
relay is damaged.
Re-energize the drive.
If the fault stays, replace the control board or the drive.
Check monitor U4-06 [SoftChgRelay Maint] shows the
performance life of the soft-charge bypass relay. If U4-06 is
more than 90%, replace the board or the drive. For information
about replacing the board, contact the manufacturer or your
nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for this fault.