EasyManuals Logo

Q2 Q2A User Manual

Q2 Q2A
866 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #669 background imageLoading...
Page #669 background image
Parameter Details
12
12.6 F: OPTIONS
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 669
The drive stops the motor during the deceleration time set in C1-02 [Decel Time 1].
After you remove the bUS alarm, the motor will accelerate to the previous frequency reference.
F6-02 Comm Ext Flt Detect (EF0)
No.
(Hex.)
Name Description
Default
(Range)
F6-02
(03A3)
Comm Ext Flt Detect (EF0)
Sets when the drive will detect EF0 [Option Card External Fault] is detected.
0
(0, 1)
0 : Always Detected
1 : Detect@RUN Only
F6-03 Comm Ext Flt Select (EF0)
No.
(Hex.)
Name Description
Default
(Range)
F6-03
(03A4)
Comm Ext Flt Select (EF0)
Sets the method to stop the motor or let the motor continue operating when the drive detects an
EF0 [Option Card External Fault].
1
(0 - 3)
0 : Ramp->Stop
The drive ramps to stop in the set deceleration time. Fault relay output terminal 1NO-1CM activates and terminal
1NC-1CM deactivates.
1 : Coast->Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal 1NO-1CM activates and
terminal 1NC-1CM deactivates
2 : Fast Stop (C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal 1NO-
1CM activates and terminal 1NC-1CM deactivates.
3 : Alarm Only
The keypad shows EF0 and the drive continues operation at the current frequency reference.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set for Alarm [H2-01 to H2-03 = 4] activates.
F6-04 bUS Err Det.Time
No.
(Hex.)
Name Description
Default
(Range)
F6-04
(03A5)
bUS Err Det.Time
Sets the delay time for the drive to detect bUS [Option Communication Error].
2.0 s
(0.0 - 5.0 s)
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
F6-06 Trq Ref/Lim Comms
No.
(Hex.)
Name Description
Default
(Range)
F6-06
(03A7)
Trq Ref/Lim Comms
Sets the function that enables and disables the torque reference and torque limit received from the
communication option.
0
(0, 1)
0 : Disabled
1 : Enabled
F6-07 Multi-Ref@NetRef/ComRef
No.
(Hex.)
Name Description
Default
(Range)
F6-07
(03A8)
Multi-Ref@NetRef/
ComRef
Sets the function that enables and disables the multi-step speed reference when the frequency
reference source is NetRef or ComRef (communication option card or Modbus communications).
0
(0, 1)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Q2 Q2A and is the answer not in the manual?

Q2 Q2A Specifications

General IconGeneral
BrandQ2
ModelQ2A
CategoryController
LanguageEnglish