12.7 H: TERMINALS
728 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Note:
When L6-01 5, the drive will detect when the output current/torque is less than the detection level of L6-02 for longer than the time
set in L6-03.
Refer to L6: TORQUE DETECTION for more information.
33: TrqDetect1NC
Setting Function Description
33 TrqDetect1NC
The terminal deactivates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than the torque value set with L6-02 [Trq Det1 Level], or
the level is less than the torque value set with L6-02 for longer than the time set with L6-03 [Trq
Det1 Time].
Note:
When L6-01 5, the drive will detect when the output current/torque is less than the detection level of L6-02 for longer than the time
set in L6-03.
Refer to L6: TORQUE DETECTION for more information.
37: TrqDetect2NO
Setting Function Description
37 TrqDetect2NO
The terminal activates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
ON : The output current/torque is more than the torque value set with L6-05 [Trq Det2 Level], or
the level is less than the torque value set with L6-05 for longer than the time set with L6-06 [Trq
Det2 Time].
Note:
When L6-04 5, the drive will detect when the output current/torque is less than the detection level of L6-05 for longer than the time
set in L6-06.
Refer to L6: TORQUE DETECTION for more information.
38: TrqDetect2NC
Setting Function Description
38 TrqDetect2NC
The terminal deactivates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than the torque value set with L6-05 [Trq Det2 Level], or
the level is less than the torque value set with L6-05 for longer than the time set with L6-06 [Trq
Det2 Time].
Note:
When L6-04 5, the drive will detect when the output current/torque is less than the detection level of L6-05 for longer than the time
set in L6-06.
Refer to L6: TORQUE DETECTION for more information.
39: Timer Output
Setting Function Description
39 Timer Output
Use this setting when the drive uses the timer function as an output terminal.
Note:
Refer to b4: TIMER for more information.
3C: Comparator 1
Setting Function Description
3C Comparator 1
The monitor value set with H2-20 [Compare1 Mon.Selection] is on while in range of the time set with H2-24 [Compare1 On-
Delay Time] and the values of H2-21 [Compare1 Low Limit] and H2-22 [Compare1 Up Limit] are in range.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV