8.7.5 Analog Output Terminal
E1.30 FM1 analog output selection
Setting range 0 ~ 7
Minimum unit 1
Factory default 0
E1.31 FM1 channel mode
Setting range 0: 0 ~ 10 V; 1: 2 ~ 10 V
Minimum unit 1
Factory default 0
E1.32 FM1 gain setting
Setting range 0.00 ~ 10.00
Minimum unit 0.01
Factory default 1.00
E1.33 ~ E1.40: Reserved
● E1.30 is used to define the function of analog outputs, as shown below:
[E1.30]=0: Output frequency. 0 ~ 10 V / 2 ~ 10 V, represents 0 ~ max. fre-
quency [b1.05]
[E1.30]=1: Set frequency. 0 ~ 10 V / 2 ~ 10 V, represents 0 ~ max. frequency
[b1.05]
[E1.30]=2: Output current. 0 ~ 10 V / 2 ~ 10 V, represents 0 ~ 2 x (rated cur-
rent)
[E1.30]=3: Reserved
[E1.30]=4: Output voltage. 0 ~ 10 V / 2 ~ 10 V, represents 0 ~ 1.2 x (rated
voltage
*
)
[E1.30]=5: Output power. 0 ~ 10 V / 2 ~ 10 V, represents 0 ~ 1.2 x (rated
power)
[E1.30]=6: Analog input voltage. 0 ~ 10 V / 2 ~ 10 V, represents 0 ~ 10 V
[E1.30]=7: Analog input current. 0 ~ 10 V / 2 ~ 10 V, represents 4 ~ 20 mA
*
: Frequency converter rated voltage is defined in parameter b0.20.
● E1.31 is used to select output signals 0 ~ 10 V or 2 ~ 10 V.
● E1.32 means the gain applied to analog output voltage.
For example: When the gain value is 0.00, then the analog output voltage will
be 0 V. In the case of "FM1 channel mode" [E1.31]=1: 2 ~ 10 V and source val-
ue is 0,
– if gain=1.00, the analog output voltage will be 2 V.
– if gain=5.00, the analog output voltage will be 10 V.