[S3.15] = 0: the frequency converter will remain static, even if a running com-
mand exists after power on. To start the frequency converter, please cancel
and reactivate the running command.
If the frequency converter was running in 3-wire control mode be-
fore power fault, the restart of the frequency converter after pow-
er on depends on the state of the 3-wire terminal which is respon-
sible for STOP.
If the frequency converter was running before power fault due to
a power supply interference, UE-1 will occur in undervoltage sit-
uation, the frequency converter will not restart automatically after
input power supply recovers even [S3.15] = 1. This is different
from the restarting by automatic fault reset, see details in E4.15
and E4.16.
During the waiting time after power on, if the active run command
source is from communication and there is request on the com-
munication to stop the frequency converter, the frequency con-
verter will not restart automatically.
8.5.4 Brake Chopper Control
S3.20 Brake chopper action point
Setting range 200 V class: 300 ~ 390 V; 400 V class: 600 ~ 885 V
Minimum unit 1 V
Factory default 200 V class: 390 V; 400 V class: 885 V
S3.21 Braking duty cycle
Setting range 1 % ~ 100 %
Minimum unit 1 %
Factory default 100 %
S3.22 ~ S3.29: Reserved
EFC 3600 Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT03-EN-P
85/259