8.10.2 Error Reset
E4.15 Number of error reset attempts
Setting range 0 ~ 3
Minimum unit 1
Factory default 0
E4.16 Interval between reset attempts
Setting range 2 ~ 60s
Minimum unit 1s
Factory default 10s
E4.17 ~ E4.19: Reserved
Automatic error reset function is used to ensure continuous running without hu-
man intervention in the case of occasional errors, such as overcurrent and over-
voltage at start-up and in run mode. This function can be activated by setting
E4.15 to a non-zero value.
When an error occurs, the frequency converter stops the output and the respec-
tive error code is displayed at the same time. The system remains in idle mode
for delay time [E4.16]. Then the error will be automatically reset and a run com-
mand will be generated to restart the frequency converter. This sequence will
be performed [E4.15] times in a row. If the error still exists, the frequency con-
verter remains in idle mode and stops performing automatic restart attempts. In
this case, a manual error reset is required to resume the operation.
Automatic error reset is valid for the following errors: OC-1, OC-2, OC-3, OE-1,
OE-2, OE-3, OE-4, OL-1, OL-2, UE-1, E-St, OH and UH.
8.10.3 Error Code Memory
E4.20 Last error type
Display range 0 ~ 51
E4.21
2
nd
last error type
Display range 0 ~ 51
E4.22
3
rd
last error type
Display range 0 ~ 51
E4.23 ~ E4.29: Reserved
Used to record the recent three errors which can be viewed after reset. For
error types, please refer to chapter 9.5.1 "Error Description and Solution" on
page 126.