8.2.3 Starting configuration
b1.30 Starting mode
Setting range 0 ~ 2
Minimum unit 1
Factory default 0
b1.31 Starting frequency
Setting range 0.00 ~ 50.00 Hz
Minimum unit 0.01 Hz
Factory default 0.05 Hz
b1.32 Starting frequency holding time
Setting range 0.0 ~ 20.0s
Minimum unit 0.1s
Factory default 0.1s
b1.33 Starting DC braking time
Setting range 0.0 ~ 20.0s (0.0 represents no action of starting DC braking)
Minimum unit 0.1s
Factory default 0.0s
b1.34 Starting DC braking current
Setting range 0.0 % ~ 150.0 % (of rated frequency converter current)
Minimum unit 0.1 %
Factory default 0.0 %
b1.35 ~ b1.39: Reserved
● [b1.30]=0: Start directly
This mode is suitable for circumstances with high static friction torque and
low load inertia.
The frequency converter runs at "Starting frequency" [b1.31], for "Starting
frequency holding time" [b1.32], and accelerates to set frequency with de-
fined acceleration time.