● If the set frequency is in the hysteresis range (including the boun-
daries) of defined skip frequency, the frequency is set to upper /
lower limit of skip frequency range;
● If the skip frequency range is set to 0.00 Hz, no skip frequency
control is enabled;
● Do not make the 3 frequency ranges overlap or nest in each oth-
er.
S3.09 Skip window acceleration factor
Setting range 1 ~ 100
Minimum unit 1
Factory default 1
S3.10 ~ S3.14: Reserved
This parameter makes the acceleration inside the skip-window faster, with the
range from 1 (normal acceleration) to 100 (acceleration is 100 times faster).
The resulting acceleration and deceleration time will be shorter than
the set value when the factor is above 1.
8.5.3 Restarting after Power Fault
S3.15 Restarting after power fault
Setting range 0 ~ 1
Minimum unit 1
Factory default 0
S3.16 Waiting time for restarting after power fault
Setting range 0.0 ~ 10.0s
Minimum unit 0.1s
Factory default 1.0s
S3.17 ~ S3.19: Reserved
● [S3.15] = 0: Prohibited. No restarting after power fault.
● [S3.15] = 1: Allowed. Restarting after power fault.
If [b1.02] = 0 (RUN command source is from panel), and the frequency convert-
er was running before power off:
● [S3.15] = 1: the frequency converter will automatically start after waiting for
the time set by S3.16 without pressing the Run key again after power on.
● [S3.15] = 0: the frequency converter only starts after the Run key is pressed.
If other RUN command source is selected ([b1.02] ≠ 0):
● [S3.15] = 1: the frequency converter will automatically start after waiting for
the time set by S3.16 only if a running command exists after power on.