8.1.2 System Configuration
b0.05 Parameter initialization
Setting range 0 ~ 2
Minimum unit 1
Factory default 0
Used to restore parameters to factory defaults. A frequency converter can re-
cord the recent 3 errors and the relevant variables for the last error for error di-
agnosis. They can be deleted if necessary.
● 0: No action
● 1: Restore to factory defaults
All parameters are restored to factory defaults except S2.00 ~ S2.15 (motor
parameters), E4.20 ~ E4.22, E4.30 ~ E4.35 (error messages) and b0.40 (sys-
tem running time).
● 2: Delete error records
Clearing parameters E4.20 ~ E4.22, E4.30 ~ E4.35.
After this command is executed completely, parameter b0.05 will be
set to zero automatically.
b0.06 Parameter replication
Setting range 0 ~ 2
Minimum unit 1
Factory default 0
b0.07 ~ b0.19: Reserved
● 0: No action
● 1: Backup parameters from frequency converter to panel
All parameters, except read-only parameters
*
and b0.40 "Cumulative running
time", are copied from the frequency converter to the operating panel.
● 2: Restore parameters from panel to frequency converter
All parameters, except read-only parameters
*
and b0.40 "Cumulative running
time", are copied from the operating panel to the frequency converter.
●
*
Read-only parameters: all monitoring parameters d0.00 ~ d0.20;
all error memory parameters E4.20 ~ E4.22 and E4.30 ~ E4.35.
● After the command is executed completely, parameter b0.06 will
be set to zero automatically and "b0.20" will be displayed.
● Any of other operations is invalid during parameter replication.
Bosch Rexroth AG
Parameter Settings
EFC 3600
48/259
DOK-RCON03-EFC-3600***-IT03-EN-P