8.1.2 System Configuration
b0.05 Parameter initialization
Setting range 0 ~ 2
Minimum unit 1
Factory default 0
Used to restore parameters to factory defaults. A frequency converter can re-
cord the recent 3 errors and the relevant variables for the last error for error di-
agnosis. They can be deleted if necessary.
0: No action
1: Restore to factory defaults
All parameters are restored to factory defaults except S2.00 ~ S2.15 (motor
parameters), E4.20 ~ E4.22, E4.30 ~ E4.35 (error messages) and b0.40 (sys-
tem running time).
2: Delete error records
Clearing parameters E4.20 ~ E4.22, E4.30 ~ E4.35.
After this command is executed completely, parameter b0.05 will be
set to zero automatically.
b0.06 Parameter replication
Setting range 0 ~ 2
Minimum unit 1
Factory default 0
b0.07 ~ b0.19: Reserved
0: No action
1: Backup parameters from frequency converter to panel
All parameters, except read-only parameters
*
and b0.40 "Cumulative running
time", are copied from the frequency converter to the operating panel.
2: Restore parameters from panel to frequency converter
All parameters, except read-only parameters
*
and b0.40 "Cumulative running
time", are copied from the operating panel to the frequency converter.
*
Read-only parameters: all monitoring parameters d0.00 ~ d0.20;
all error memory parameters E4.20 ~ E4.22 and E4.30 ~ E4.35.
After the command is executed completely, parameter b0.06 will
be set to zero automatically and "b0.20" will be displayed.
Any of other operations is invalid during parameter replication.
Bosch Rexroth AG
Parameter Settings
EFC 3600
48/259
DOK-RCON03-EFC-3600***-IT03-EN-P