Motor physical data
Code Name Setting range Min. unit Default Attri.
S2.10 Stator resistance
0.00 ~ 50.00 Ω 0.01 Ω
Depends
on model
STOP
S2.11 Rotator resistance
S2.12 Leakage inductance 0.00 ~ 200.00 mH 0.01 mH STOP
S2.13 Mutual inductance 0.0 ~ 3,000.0 mH 0.1 mH STOP
S2.14 No-load current 0.0 A ~ [S2.04] 0.1 A STOP
S2.15
Physical data
calculation
0: No action
1: Calculation
2: Automatic adjustment while the
motor is in static mode
3: Automatic adjustment while the
motor is rotating
1 0 STOP
S2.16 ~ S2.19 Reserved
Motor thermal protection
Code Name Setting range Min. unit Default Attri.
S2.20 Sensor type 0: PTC; 1: NTC 1 0 STOP
S2.21 Input channel of motor temperature
0: Invalid
1: Analog input
voltage
1 0
S2.22 Protection level 0.0 ~ 10.0 0.1 2.0 STOP
S2.23 Thermal motor time constant 0.0 ~ 400.0 min 0.1 min
Depends
on model
STOP
S2.24 ~ S2.39 Reserved
17.2.6 Group S3: Running Parameters
Jogging parameters
Code
Name Setting range Min. unit Default Attri.
S3.00 Jogging frequency 0.00 Hz ~ [b1.05] 0.01 Hz 5.00 Hz RUN/STOP
S3.01 Jogging acceleration time 0.1 ~ 6,000.0s 0.1s 5.0s RUN/STOP
S3.02 Jogging deceleration time 0.1 ~ 6,000.0s 0.1s 5.0s RUN/STOP
S3.03 ~ S3.04 Reserved