17.2.2 Group b0: System Parameters
Password and access control
Code Name Setting range Min. unit Default Attri.
b0.00 User password 0 ~ 65535 1 0 RUN/STOP
b0.01
Manufacturer
password
0 ~ 65535 1 0 STOP
b0.02 Access authority setting
0: Basic parameters
1: Standard parameters
2: Extended parameters
3: Advanced parameters
4: Start-up mode
1 0 RUN/STOP
b0.03, b0.04 Reserved
System configuration
Code Name Setting range Min. unit Default Attri.
b0.05 Parameter initialization
0: No action
1: Restore to factory default
2: Remove error records
1 0 STOP
b0.06 Parameter replication
0: No action
1: Backup parameters from fre-
quency converter to panel
2: Restore parameters from panel
to frequency converter
1 0 STOP
b0.07 ~ b0.19 Reserved
For parameters b0.05 and b0.06, the value is automatically set to be
0 after the operation.