H0.03 Local address
Setting range ModBus: 1 ~ 247; PROFIBUS: 1 ~ 126
Minimum unit 1
Factory default 1
H0.04 ~ H0.07: Reserved
● In ModBus communication, the maximum number of frequency converters in
the network is 247 (0 is broadcast address).
● In PROFIBUS communication,
– the maximum number of frequency converters in the network is 126.
– local address change with any of the slaves requires re-power of that slave.
H0.08 Communication disruption detection time
Setting range 0.0 ~ 60.0s
Minimum unit 0.1s
Factory default 0.0s
H0.09 Communication disruption action
Setting range 0 ~ 1
Minimum unit 1
Factory default 1
When [H0.08] = 0.0s, the disruption detection is disabled, otherwise the detec-
tion is enabled.
If the interval between the current communication and the next exceeds the
time defined in H0.08, a communication error / warning is reported and the ac-
tion is defined by H0.09:
● 0: The motor freewheels to stop after the communication timeout no matter
the settings of parameter b1.40 "Stopping mode".
● 1: The motor continues running at the set frequency. For error / warning mes-
sage, see chapter 9 "Diagnosis" on page 124.
H0.10 ~ H0.17
PZD3 ~ PZD10 setting
Setting range 0 ~ 20
Minimum unit 1
Factory default 0
Used to set monitoring parameters of PZD (slave to master) area in PROFIBUS
communication, see chapter 17.2.13 "Group d: Monitoring Parameters" on page
241.
EFC 3600
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT03-EN-P
123/259