OH: Frequency converter over temperature
Possible reason Solution
Frequency converter (heat sink) tem-
perature is higher than max. allowable
temperature 85 °C
Reduce ambient temperature, improve ventilation and
heat dissipation; clear dust, cotton wadding in air ducts;
check fan and its power supply connection (if available)
Reduce load if necessary
Reduce carrier frequency (b0.21)
Temperature detection circuit error Contact with service
CPUC: I/O board trap error
Possible reason Solution
Fatal error with CPU on I/O board
Check the wiring of control circuit, main circuit and
grounding to find out the source of interference
If it happens again, contact with service
CPUE: Operating panel trap error
Possible reason Solution
Fatal error with CPU on operating panel
Check the wiring of control circuit, main circuit and
grounding to find out the source of interference
If it happens again, contact with service
CE3-: SPI problem between operating panel board and I/O board
Possible reason Solution
Problem with operating panel
Check the wiring of control circuit, main circuit and
grounding to find out the source of interference
If it happens again, replace the operating panel or contact
with service
CE4-: Internal problem on operating panel
Possible reason Solution
Problem with operating panel
Check the wiring of control circuit, main circuit and
grounding to find out the source of interference
If it happens again, replace the operating panel or contact
with service
EFC 3600 Bosch Rexroth AG
Diagnosis
DOK-RCON03-EFC-3600***-IT03-EN-P
131/259