In this case, [d0.07] will be displayed when the frequency converter is in
running monitoring mode.
The setting of parameter b0.31 decides which parameter of group d will be dis-
played in stop monitoring mode.
Example 2: [b0.31]=8
In this case, [d0.08] will be displayed when the frequency converter is in
stop monitoring mode.
b0.32 User-defined proportion factor for velocity
Setting range 0.01 ~ 100.0
Minimum unit 0.01
Factory default 1.00
b0.33 PID reference / feedback coefficient
Setting range 0.01 ~ 100.0
Minimum unit 0.01
Factory default 1.00
Used for monitoring function. They only affect the displayed value of monitoring
parameters regarding velocity or PID control parameters.
User-defined set velocity
[d0.10] = [d0.02] x [b0.32]
With:
[d0.10]: User-defined set velocity
[d0.02]: Set frequency
[b0.32]: User-defined proportion factor for velocity
User-defined output velocity
[d0.11] = [d0.00] x [b0.32]
With:
[d0.11]: User-defined output velocity
[d0.00]: Output frequency
[b0.32]: User-defined proportion factor for velocity
Users may convert the frequency to any other form they feel easy to understand
via parameter b0.32.
PID reference engineering value
[d0.14] = PID reference x [b0.33]
With:
[d0.14]: PID reference engineering value
[b0.33]: PID reference / feedback coefficient
PID feedback engineering value
EFC 3600
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT03-EN-P
51/259