value of this parameter is a percentage of the frequency converter rated tor‐
que.
Group S2: Motor and encoder parameters
S2.00
Rated motor frequency Factory default 50.00
Setting range 8.00...400.00 Hz Minimum unit 0.01
S2.01
Rated motor rotation speed Factory default 1,440
Setting range 1...24,000 rpm Minimum unit 1
S2.02
Rated motor power Factory default
Depends on
model
Setting range 0.4...1,000.0 kW Minimum unit 0.1
S2.03
Rated motor voltage Factory default
Depends on
model
Setting range 0...900 V Minimum unit 1
S2.04
Rated motor current Factory default
Depends on
model
Setting range 0.1...1,000.0 A Minimum unit 0.1
Set parameters S2.00...S2.04 according to the nameplate of the motor. The
rated motor power should be the same or one class lower than the rated
power of the frequency converter. Otherwise the performance could be affec‐
ted.
S2.05
Stator resistance factor Factory default
Depends on
model
Setting range 0.00...50.00 % Minimum unit 0.01
S2.06
Rotor resistance factor Factory default
Depends on
model
Setting range 0.00...50.00 % Minimum unit 0.01
S2.07
Leakage inductance factor Factory default
Depends on
model
Setting range 0.00...50.00 % Minimum unit 0.01
S2.08
Mutual inductance factor Factory default
Depends on
model
Setting range 0.0...2,000.0 % Minimum unit 0.1
S2.09
No-load current Factory default
Depends on
model
Setting range 0.0...1,000.0 A Minimum unit 0.1
S2.10
Parameter auto-tuning Factory default 0
Setting range 0...2 Minimum unit 1
The motor parameters (S2.00...S2.04) must be set according to the motor
nameplate before using ‘Parameter auto-tuning’ [S2.10].
● [S2.10] = 0: No action
● [S2.10] = 1: Auto tuning with running motor
DOK-RCON02-FV*********-IB08-EN-P Bosch Rexroth AG 121/259
Rexroth Frequency Converter Fv
Parameter Settings