7.3 Parameters Functions
7.3.1 Category b: Basic Parameters
Group b0: System parameters
Code Name Setting range Min.unit Default Attrib.
b0.00 User password 0...65,535 1 0 ◇
b0.01 LCD language 0: Chinese; 1: English 1 0 ◇
b0.02 Restore factory default
0: No action
1: Restore parameters to factory default
Note: The value is automatically set to 0 after restor‐
ing factory default.
1 0 ◆
b0.03 Parameter copy
0: No action
1: Copy from frequency converter to operating panel
2: Copy from operating panel to frequency converter
Note: The value is automatically set to 0 after param‐
eter copy.
1 0 ◆
b0.04 Mains voltage 380...480 V 1 380 ◆
b0.05 PWM frequency 1.0...15.0 kHz 0.1
Depends
on model
◇
b0.06
Automatic adjustment of
PWM frequency
0: OFF; 1: On 1 1 ◆
b0.07 LCD backlight mode 0: Energy saving; 1: Always on 1 0 ◇
b0.08 LCD display in run mode
0...17
1 0 ◇
b0.09 LCD display in stop mode 1 2 ◇
b0.10
Scale factor of user-defined
value
0.1...1,000.0 % 0.1 100.0 ◇
b0.11 Parameter filter setting
0: b Parameters; 1: b, S Parameters
2: b, S, E Parameters; 3: b, S, E, H Parameters
1 0 ◇
b0.12 Heat sink temperature 25...100 °C 1 Measured ◎
b0.13 Total running time 0...65,535 hours 1 0 ◎
b0.14 Firmware version Read-only – – ◎
b0.15 Reserved 0, 1 1 0 ◆
Setting range of parameters b0.08 and b0.09:
0: Output frequency; 1: Output rotation speed; 2: Set frequency
3: Set rotation speed; 4: Output voltage; 5: Output current
6: Output power; 7: DC bus voltage; 8: Torque current
9: Excitation current; 10: User-defined reference value
11: User-defined output value; 12: Reference torque
13: Digital inputs status; 14: Encoder speed feedback
15: Torque limit setting; 16: Speed limit setting; 17: Multi-monitoring display
DOK-RCON02-FV*********-IB08-EN-P Bosch Rexroth AG 83/259
Rexroth Frequency Converter Fv
Parameter Settings