7.4 Notes on Function Groups
7.4.1 Category b: Basic Parameters
Group b0: System parameters
b0.00
User password Factory default 0
Setting range 0...65,535 Minimum unit 1
User password protects frequency converter parameters from being modified
by unauthorized people.
● Set password: Set a number between 1...65,535 to activate the user
password function.
● Delete password: Enter the correct user password and set [b0.00] = 0 to
deactivate the password.
● Modify password: Enter the correct user password and set a new num‐
ber between 1...65,535 to modify the user password.
1. After a user password has been set, users may only read
but not modify nor copy parameters if an incorrect password
is entered.
2. Please contact the manufacturer if you forget the set pass‐
word.
b0.01
LCD language Factory default 0
Setting range 0, 1 Minimum unit 1
LCD / Menu language is available in
● 0: Chinese
● 1: English
b0.02
Restore factory default Factory default 0
Setting range 0, 1 Minimum unit 1
● 0: No action
● 1: Restore factory default
1. All parameters (except S2.00...S2.09 and E4.13...E4.15) will
be restored to factory defaults.
2. b0.02 is automatically set to 0 after the parameters have
been set to factory defaults.
b0.03
Parameter copy Factory default 0
Setting range 0...2 Minimum unit 1
● 0: No action
● 1: Copy parameters from frequency converter to operating panel
Parameter settings of the frequency converter (except E4.13...E4.15)
will be uploaded to the operating panel.
● 2: Copy parameters from operating panel to frequency converter
Parameter settings of the frequency converter (except E4.13...E4.15)
will be downloaded to the frequency converter.