Installation
Lethal electric shock caused by live parts with
more than 50 V!
Before working on live parts: De-energize the installation and secure the
power switch against unintentional or unauthorized re-energization.
Wait at least 30 minutes after switching off the power supply voltages to allow
discharging.
Check whether voltages have fallen below 50 V before touching live parts!
Risk of damage by intense heat!
During the discharging process, the discharging resistor generates intense
heat. Therefore, place the discharging resistor as far as possible from heat-
sensitive components.
How to install the discharging device
1. Preferably install discharging device before switching on supply voltage
of the first time.
If you install discharging device after having switched on supply voltage
for the first time, wait 30 minutes to allow discharging. Check whether
voltage has fallen below 50 V before touching live parts!
2. Place discharging resistor as far as possible from heat-sensitive compo‐
nents.
Activation
Observe the following order for activating the discharge device:
1. De-energize installation and secure power switch against unintentional
or unauthorized re-energization.
2. Activate discharging device.
DOK-RCON02-FV*********-IB08-EN-P Bosch Rexroth AG 215/259
Rexroth Frequency Converter Fv
Additional Information